Choosing a 1 kW-class industrial AC-DC power supply starts with the actual load, cooling arrangement, and installation constraints. The K19H-UP1000S series gives equipment teams five fixed-output options from 12 V to 48 V in a compact chassis. TPS ELECTRIC LLC offers these products and supports B2B customers worldwide with selection, engineering consultation, and integration discussions.
For system integrators, panel builders, electrical engineers, and procurement teams, the key distinction is simple: the 12 V model delivers 900 W, while the 24 V, 28 V, 36 V, and 48 V models are rated at 1008 W. Neither rating should be treated as unconditional output in every enclosure. This guide turns the specification into a practical shortlist and an RFQ that TPS can evaluate against your project.
Select the nominal rail first, then verify continuous current and the allowed load envelope. The series includes active power factor correction (PFC), a 90-264 VAC input range, and a listed efficiency of 93% at 230 VAC. The following values come from the supplied product specification; model links lead directly to TPS quotation pages.
| TPS model / product page | Output | Rated current | Rated power | Ripple and noise |
|---|---|---|---|---|
| K19H-UP1000S12 | 12 VDC | 75 A | 900 W | 200 mVp-p |
| K19H-UP1000S24 | 24 VDC | 42 A | 1008 W | 300 mVp-p |
| K19H-UP1000S28 | 28 VDC | 36 A | 1008 W | 300 mVp-p |
| K19H-UP1000S36 | 36 VDC | 28 A | 1008 W | 360 mVp-p |
| K19H-UP1000S48 | 48 VDC | 21 A | 1008 W | 480 mVp-p |
A useful comparison must include voltage tolerance, current, ripple, mechanical fit, and recovery behavior. A lower purchase price does not compensate for an unsuitable DC rail or a cabinet that cannot remove the heat. Ask TPS to review these constraints together before approving the production bill of materials.
Figure 1. The 12 V version is 900 W; the other four versions are 1008 W under the specified operating conditions.
The 12 V / 75 A option is a candidate for high-current equipment rails and fixed-voltage test fixtures. At 75 A, cable resistance and termination quality become major design inputs. The 24 V / 42 A model suits evaluation for automation equipment and centralized DC distribution where every connected load accepts the selected voltage.
Choose the 28 V / 36 A version when the equipment specifically requires a 28 V rail. The 36 V / 28 A supply is another option for compatible actuators or embedded equipment. The 48 V / 21 A model can serve compatible 48 V subsystems with lower current than a lower-voltage rail at equal power. These are application candidates, not approvals for every load.
All five models list ±5% output adjustment, ±1% output accuracy, and ±0.5% line and load regulation. Trim is for setting a rail within the allowed range; it does not establish programmable operation or additional power capacity. Confirm the permissible current when using an adjusted voltage. The specification does not establish remote sensing, digital control, or parallel current sharing.
As an engineering example, a 24 V load drawing 30 A continuously requires 720 W. That is below the 1008 W nameplate, but the available margin changes with input voltage and cooling. Document startup duration, simultaneous loads, capacitive charging, and transient current. The 105-150% overload protection band is not a guaranteed peak-power allowance.
Use the specified ripple limits against the load requirement. The datasheet measures ripple with a 30 cm twisted connection, 0.1 µF and 47 µF capacitors at the load, and a 20 MHz oscilloscope bandwidth. A different harness or measurement arrangement may give different results. Sensitive circuitry may need local regulation or filtering, confirmed by equipment testing.
Rated input is 100-240 VAC at 50-60 Hz; the operating range is 90-264 VAC. Listed input current is 5 A at 230 VAC and 11 A at 110 VAC, with a 60 A cold-start inrush at 230 VAC. Coordinate upstream protection using the actual installation and approved data. Power factor is listed above 0.98 at 100 V and above 0.95 at 230 V.
Setup/rise/hold-up times are 500/30/5 ms at 115 VAC and 300/30/10 ms at 230 VAC. If a controller must ride through longer interruptions, evaluate a separate backup architecture. A wide input range alone does not provide uninterrupted output.
Figure 2. Check usable output and system behavior before treating the wattage rating as a purchasing decision.
The specification distinguishes operation with and without a fan. Its thermal curve indicates approximately 100% load with fan cooling up to 50°C, followed by derating toward 60°C. Without a fan, the curve shows about an 80% load baseline, with further derating above roughly 40°C. These are approximate graph readings; obtain confirmed limits for your installation.
The input-voltage curve also matters: with a fan, the plotted load rises from approximately 80% at 90 VAC to 100% around 115 VAC. Fanless operation is shown near 80% across the illustrated input range, subject to thermal restrictions. Do not multiply separate curve values or assume which limit governs without clarification. Ask TPS to confirm the combined operating envelope and required airflow.
The working temperature range is -20°C to 60°C, with 10-90% RH and no condensation. This range does not mean full output throughout. For the 24 V example, an 80% allowance corresponds to 806.4 W before any further applicable restrictions. A 720 W load could therefore have much less reserve than the nameplate comparison suggests.
Overall dimensions are 214 × 82 × 48 mm, with a listed weight of 1.2 kg. Use the dimensional drawing to approve the mounting pattern. When mounting from the bottom, screw penetration into the supply must not exceed 4 mm. Account for plate thickness, screw length, and service access before releasing fabrication drawings.
The input terminal is identified as 3P-8.25. The 12 V, 24 V, and 28 V models use 2P M5 copper screw output terminals; the 36 V and 48 V models use 4P (8.25) terminals. Confirm the exact pin assignment, allowable conductors, and tightening torque. Terminal descriptions alone do not define the approved wiring arrangement.
Plan protective-earth bonding, branch protection, strain relief, touch protection, and cable routing around the exposed assembly. The supplied specification gives no enclosure ingress-protection rating. TPS can discuss custom cable and harness support and enclosure integration for the complete equipment.
Figure 3. Approximate load-curve readings guide the initial review; confirm airflow and combined derating with TPS.
Overload protection is specified at 105-150% with hiccup operation and automatic recovery. Output short circuit uses lock protection, requiring power to be turned off for five minutes before restoration. Overvoltage protection is listed at 120-140% of output voltage with the same power-off reset requirement. Plan the service procedure and restart sequence accordingly.
Brownout protection is listed at 70 VAC with automatic recovery. Overtemperature protection shuts down output when shell temperature exceeds 115°C and restores automatically. That shutdown threshold is not a permitted design temperature. Equipment-level controls should address unwanted restart, fault indication, and loss of DC power according to the application.
The datasheet lists GB4943, EN60950-1, and EN62368-1 under safety, and GB/T9254-2008, GB17625.1-2012, EN55032 Class B, and EN61000-3-2 under EMC. These references support a documentation review; they do not establish a current third-party certificate, UL listing, or approval of the finished cabinet. Request model-specific reports and the applicable editions for the destination market.
Listed withstand voltage is 3 kVAC input-to-output, 1.8 kVAC input-to-frame ground, and 0.6 kVAC output-to-frame ground for one minute. Leakage current is below 0.75 mA at 240 V. Verify how these values fit the equipment safety architecture. EMC behavior must also be assessed with the intended enclosure, grounding, wiring, and connected loads.
MTBF is stated as greater than 50,000 hours using MIL-HDBK-217F at 25°C. It is a calculated reliability indicator, not a warranty or guaranteed service life. The datasheet generally references measurements at 230 VAC, rated load, 25°C ambient, and 70% humidity unless otherwise specified. Procurement should retain the approved specification and acceptance requirements with the purchase order.
Figure 4. Automatic recovery and power-off reset are different behaviors; verify that both fit your operating procedure.
TPS can supply the K19H-UP1000S models and help assess related products or an equivalent solution when a project needs a different interface, operating envelope, or architecture. Selection support can extend to engineering consultation and project-level integration. Product customization and special configurations require a feasibility review rather than an assumption that every feature is available.
For a complete build, TPS provides related power-electronics manufacturing services and industrial control cabinet solutions. Discuss the scope as a coordinated package: power supply, mechanical enclosure, harnesses, assembly, and agreed verification. This gives project managers and procurement a clearer basis for comparing component-only and integrated quotations.
Ask TPS to confirm availability, lead time, MOQ, warranty terms, documentation, and quotation validity. These commercial details are not specified in the supplied datasheet. For recurring production, also discuss revision control, approved samples, and change notification. Attach a load profile and drawing so the response can address technical fit as well as price.
Request a Model-Specific Quote From TPS
Start with the rail your equipment requires: 12 V high-current supply, 24 V automation supply, 28 V equipment supply, 36 V DC supply, or 48 V industrial supply. On the selected product page, use the quotation inquiry and include your project requirements. TPS can then review the model, integration scope, and delivery assumptions together.
Figure 5. A complete RFQ helps TPS confirm the product and project scope before procurement commits.
No. The 12 V / 75 A version is rated at 900 W. The 24 V, 28 V, 36 V, and 48 V versions are each rated at 1008 W. Available output also depends on input and cooling conditions.
The supplied curves do not support unconditional full-power fanless use. They show approximately 80% load without a fan and further thermal derating at higher temperatures. Confirm airflow and allowable load for your enclosure with TPS.
The specification describes a latched short-circuit shutdown requiring power off for five minutes before restoration. Overvoltage uses the same reset approach. Overload, brownout, and overtemperature have different specified recovery behaviors.
Parallel current sharing, remote sensing, and digital control are not established by the supplied specification. Include these needs in the RFQ so TPS can evaluate a suitable configuration or another power solution.
Request the approved model specification, required safety and EMC evidence, confirmed operating limits, and agreed acceptance criteria. Also obtain pricing, availability, lead time, MOQ, warranty terms, and shipment details for the actual quantity and destination.
EA-PUB 10000 4U Series: 30 kW Bidirectional DC Power for Scalable Test Systems
EA-EL 9000 B Series: Programmable DC Loads for Industrial Test Systems
TBM800-53KTIT Industrial Applications: 53 kW Bidirectional Power for Battery Test and Regenerative Aging
YB-D Series Compliance & Testing: Qualify EMI Filters for Industrial Control Panels
EA-PS3000 C Series Power Design Guide: Select and Integrate a DC Test Bench Supply
EA-PS 10060-120 2U: 60 V, 120 A, 3 kW Programmable DC Power Supply
EA-PS 9080-50 1U: 1500 W Programmable DC Power for Test Racks
eTM-605, eTM-605F and eTM-605P Compliance Guide: Qualify 60V Bench Power Supplies for Lab and Production Testing